Authors
Hwan-Jong Choi, Byung-Soon Kim, Donghoon Kang, Kyung Chun Kim
Publication date
2011/12/1
Journal
Applied Energy
Volume
88
Issue
12
Pages
4544-4555
Publisher
Elsevier
Description
A novel dual hot gas bypass defrosting (DHBD) method is developed to remove frost from the outside heat exchanger (HEX) of an air-to-air heat pump. The proposed method adopts two bypass lines of hot gas from the compressor: one is connected to the inlet of the outdoor HEX, and the other is connected to the outlet of the exchanger. We compare the dynamic performance and defrosting time of the conventional reverse cycle defrosting (RCD), hot gas bypass cycle defrosting (HGBD), and DHBD methods using a medium air-to-air 16kW heat pump. The salient feature of the DHBD method is its ability to prevent a sharp decrease in the compressor outlet temperature at the melting frost stage after the HGBD process begins. Due to the additional bypass, the DHBD method sustained a higher compressor outlet pressure and reduced the defrosting time by 36% compared to the HGBD method. Compared to RCD, the …