Authors
Pär Johansson, Carl-Eric Hagentoft, Angela Sasic Kalagasidis
Publication date
2014/4/1
Journal
Energy and Buildings
Volume
73
Pages
92-104
Publisher
Elsevier
Description
Many old listed buildings have an unsatisfactory thermal performance compared to the standards of today. The listing often limits the position and necessary thickness of an added insulation layer in the building envelope. Vacuum insulation panels (VIP) present unprecedented possibilities to reduce the required thickness of the insulation layer. The aim of this study is to explore the performance of VIP in the retrofitting of listed buildings. The goal is to improve the thermal transmittance and moisture performance of the wall and the thermal comfort for the occupants. Hygrothermal sensors were installed in the wall of a listed building insulated with VIP on the exterior. Sensors were also installed in a neighboring (non-retrofitted) wall as reference. Through a comparative analysis of the measured data it was concluded that the hygrothermal performance of the retrofitted wall was substantially better than of the reference …