Authors
G Prakash Narayan, Syed M Zubair
Publication date
2010/10/1
Journal
International Journal of Thermal Sciences
Volume
49
Issue
10
Pages
2057-2066
Publisher
Elsevier Masson
Description
This paper details a simple procedure by which the entropy generation in simultaneous heat and mass exchange devices can be minimized. Effectiveness for these devices is defined and a new parameter, ‘modified heat capacity rate ratio’ is introduced. It is found that the entropy generation of a combined heat and mass exchange device is minimized (at constant value of effectiveness) when the modified heat capacity rate ratio is equal to one irrespective of the value of other independent parameters. Several typical examples of the cooling towers have been studied to illustrate this concept. A practical application of the concept is also illustrated using a humidification–dehumidification desalination system.
Total citations
2011201220132014201520162017201820192020202120222023202491071010105202721168196