Authors
Jorge A Rivera-Cruz, Sergio F Breña, Simos Gerasimidis, Peggi L Clouston
Publication date
2021/11/1
Journal
ACI Structural Journal
Volume
118
Issue
6
Pages
203-214
Publisher
American Concrete Institute
Description
Three full-scale reinforced concrete frame sub-assemblages were tested in the laboratory to simulate the removal of an interior column. The location of bottom longitudinal reinforcement splices was varied in each specimen to evaluate ACI 318-19 detailing practices on perimeter frame beam behavior. The laboratory specimens represent two first-floor interior spans of the perimeter frame of a 10-story prototype building designed for Seismic Design Category (SDC) A. After specimens reached their peak force, a sudden decrease in force was observed due to a sudden shear failure near the exterior end of one of the beams. Failure occurred prior to the development of catenary action in the beams, a phenomenon that has been observed in similar tests of specimens detailed according to higher SDCs. The limited rotation capacity of the beams in the specimens and the shear-strength degradation as a result of diagonal …
Scholar articles
JA Rivera-Cruz, SF Breña, S Gerasimidis, PL Clouston - ACI Structural Journal, 2021